KB 0013
When I try to use the A-B Ethernet ActiveX Control with a MicroLogix 1100, I get result code 10061.


CATEGORY

ActiveX Controls

 

SYMPTOMS

When I try to use the A-B Ethernet ActiveX Control with a MicroLogix 1100, I get result code 10061.

 

RESOLUTION

MicroLogix 1100 is the first in the MicroLogix family to use EIP/CIP protocol. You must tell the ActiveX Control that the target device uses EIP/CIP.

Version 2.6 and higher: Add 'EIP:' to the NodeAddress property anywhere after the third field.

Version 2.5 and below: upgrade to current version, then follow these instructions.

 

EXAMPLE

To communicate with a MicroLogix 1100 at IP address '192.168.0.11', set the NodeAddress property as follows:

Asabtcp1.NodeAddress = "192.168.0.11,,,EIP:"

Refer to Help > Properties > NodeAddress for complete details.